Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 5, 2022, 05:09 AM
  • 01 1205_01 1204_04042022_222737.mp4

Date
04/04/2022
W/O
947045
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00226
PipeID
P02116
Time
10:09 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10053
Sewer Name
01 WILCOX AVENUE TRUNK, EXTENSION #1
City
CUDAHY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_947045_TV01206_APR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 1205
Downstream MH
01 1204
Dir. of Survey
Downstream
Length Surveyed
349.9 ft.
Total Length
349.9 ft.
Structural Index
3
Structural Quick
493J
Structural Rating
204
O&M Index
2
O&M Quick
3213
O&M Rating
9
Overall Index
3
Overall Quick
Overall Rating
213
Pipe schematic from manhole 01 1205 to 01 1204
MH: 01 1205MH: 01 1204downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 12050 ft. MWL - Water Level, 20 %of cross sectional area5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start10.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish10.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start31.9 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"32 ft. RMC - Roots Medium Connection, from 02 to 05 o'clock, 15 %, within 8 inches of joint: NO32 ft. RFL - Roots Fine Lateral, at 02 o'clock62.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"106.8 ft. RFJ - Roots Fine Joint, from 04 to 05 o'clock, within 8 inches of joint: YES133.1 ft. RFL - Roots Fine Lateral, at 02 o'clock133.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"150.8 ft. RML - Roots Medium Lateral, at 02 o'clock, 20 %, within 8 inches of joint: NO150.8 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"242.2 ft. FM - Fracture Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES288 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start288 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish296.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"298.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"330.3 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish349.9 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK349.9 ft. AMH - Downstream Manhole, Survey Ends - 01 1204

Observation photos (7)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    5 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    31.9 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Roots Medium Connection, from 02 to 05 o'clock, 15 %, within 8 inches of joint: NO

    32 ft. - Roots Medium Connection, from 02 to 05 o'clock, 15 %, within 8 inches of joint: NO

  • Roots Fine Joint, from 04 to 05 o'clock, within 8 inches of joint: YES

    106.8 ft. - Roots Fine Joint, from 04 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

    242.2 ft. - Fracture Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    288 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
0MWM
133.1RFL
31.9TB
0AMH01 1205
150.8RML
150.8TB
349.9MGOCONNECTION AT THE MH 9 OC'LOCK
32RMC
106.8RFJ
349.9AMH01 1204
10.9FL
5FL
288FM
133.1TF
10.9CM
242.2FM
0MWL
62.3TFC
296.6TFC
298.8TFC
288CM
32RFL
330.3FM

Properties (7)

additional_info
630074040422201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-04-04T22:09:41-07:00
documentation
PROPIPE
is_lateral_inspection
false