Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 5, 2022, 05:57 AM
  • 01 1203_01 1202_04042022_231203.mp4

Date
04/04/2022
W/O
947045
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00226
PipeID
P02114
Time
10:57 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10053
Sewer Name
01 WILCOX AVENUE TRUNK, EXTENSION #1
City
CUDAHY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_947045_TV01206_APR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 1203
Downstream MH
01 1202
Dir. of Survey
Downstream
Length Surveyed
201.4 ft.
Total Length
201.4 ft.
Structural Index
3
Structural Quick
3G00
Structural Rating
117
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
120
Pipe schematic from manhole 01 1203 to 01 1202
MH: 01 1203MH: 01 1202downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 12030 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK3.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start24.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"87.6 ft. TBI - Tap Break-In Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 2"120.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"162.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"173.7 ft. RFJ - Roots Fine Joint, from 03 to 04 o'clock, within 8 inches of joint: YES192.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish192.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start199 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish201.4 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK201.4 ft. AMH - Downstream Manhole, Survey Ends - 01 1202

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 2"

    87.6 ft. - Tap Break-In Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 2"

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    192.4 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
192.4FL
201.4MGOCONNECTION AT THE MH 3 OC'LOCK
3.6CM
192.3CM
199FL
201.4AMH01 1202
0AMH01 1203
120.9TF
162.3TFC
24.8TFC
0MWM
0MWL
173.7RFJ
0MGOCONNECTION AT THE MH 3 OC'LOCK
87.6TBI

Properties (7)

additional_info
630074040422201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-04-04T22:57:21-07:00
documentation
PROPIPE
is_lateral_inspection
false