Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 5, 2022, 06:13 AM
  • 01 1202_01 1201_04042022_233224.mp4

Date
04/04/2022
W/O
947045
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00226
PipeID
P02113
Time
11:13 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10053
Sewer Name
01 WILCOX AVENUE TRUNK, EXTENSION #1
City
CUDAHY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_947045_TV01206_APR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 1202
Downstream MH
01 1201
Dir. of Survey
Downstream
Length Surveyed
305.8 ft.
Total Length
305.8 ft.
Structural Index
3
Structural Quick
3D00
Structural Rating
75
O&M Index
1
O&M Quick
1B00
O&M Rating
15
Overall Index
2
Overall Quick
Overall Rating
90
Pipe schematic from manhole 01 1202 to 01 1201
MH: 01 1202MH: 01 1201downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 12020 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MWL - Water Level, 20 %of cross sectional area2.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start48.7 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start60.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"119.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish119.4 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish124.7 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK124.7 ft. MGO - General Observation - UNMAPPED MH153.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"209.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"221.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES258.7 ft. CM - Crack Multiple, from 11 to 05 o'clock, within 8 inches of joint: YES294.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"294.4 ft. RFC - Roots Fine Connection, from 07 to 09 o'clock305.8 ft. AMH - Downstream Manhole, Survey Ends - 01 1201

Observation photos (5)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    48.7 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    221.8 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 11 to 05 o'clock, within 8 inches of joint: YES

    258.7 ft. - Crack Multiple, from 11 to 05 o'clock, within 8 inches of joint: YES

  • Roots Fine Connection, from 07 to 09 o'clock

    294.4 ft. - Roots Fine Connection, from 07 to 09 o'clock

Observations (18)

DistanceCodeObservation
119.4CM
0AMH01 1202
48.7RFJ
305.8AMH01 1201
124.7MGOCONNECTION AT THE MH 9 OC'LOCK
0MWM
2.4CM
221.8FL
209.1TFC
153.3TFC
294.4RFC
258.7CM
0MGOCONNECTION AT THE MH 3 OC'LOCK
119.4RFJ
294.3TFC
60.5TFC
0MWL
124.7MGOUNMAPPED MH

Properties (7)

additional_info
630074040422201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-04-04T23:13:10-07:00
documentation
PROPIPE
is_lateral_inspection
false