Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 7, 2021, 06:23 AM
  • 18 0669_18 0668_12062021_223526.mp4

Date
12/06/2021
W/O
921605
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00696
PipeID
P14518
Time
10:23 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9554
Sewer Name
18 PHOEBE AVENUE TRUNK
City
LA MIRADA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_921605_TV18081_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
18 0669
Downstream MH
18 0668
Dir. of Survey
Downstream
Length Surveyed
349.6 ft.
Total Length
349.6 ft.
Structural Index
4
Structural Quick
4K21
Structural Rating
242
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
242
Pipe schematic from manhole 18 0669 to 18 0668
MH: 18 0669MH: 18 0668downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 06690.1 ft. MWM - Water Mark, 20 %of cross sectional area29 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES42.7 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"48.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start96.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"102.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"197.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"202.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"299.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"304.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"349.6 ft. AMH - Downstream Manhole, Survey Ends - 18 0668349.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    29 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    42.7 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    48.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
0.1MWM
197.4TFC
48.8FM
349.6AMH18 0668
0MWL
42.7TB
29CL
96.5TF
102.1TF
304.9TFC
299.7TFC
202.8TFC
349.6FM
0AMH18 0669

Properties (7)

additional_info
630074120621201
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-12-06T22:23:08-08:00
documentation
PROPIPE
is_lateral_inspection
false