Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 22, 2022, 07:17 AM
  • 15 0107_15 0106_03222022_002640.mp4

Date
03/22/2022
W/O
941303
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00590
PipeID
P11985
Time
12:17 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9930
Sewer Name
15 ABBEY STREET TRUNK
City
LA PUENTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
38
Purpose
Routine Assessment
Project
RFIR_WO_941303_TV15204_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0107
Downstream MH
15 0106
Dir. of Survey
Downstream
Length Surveyed
170.5 ft.
Total Length
170.5 ft.
Structural Index
3
Structural Quick
3E00
Structural Rating
84
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
84
Pipe schematic from manhole 15 0107 to 15 0106
MH: 15 0107MH: 15 0106downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 010731.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES35.8 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start65.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"70.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"80.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"96.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"100.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"134.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"150 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"168.8 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish170.5 ft. AMH - Downstream Manhole, Survey Ends - 15 0106

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    31.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    35.8 ft. - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
65.9TFC
100.9TF
31.5CM
80.1TF
96.9TF
134.9TFC
168.8CM
150TF
0MWM
35.8CM
0MWL
70.6TFC
0AMH15 0107
170.5AMH15 0106

Properties (7)

additional_info
630074032122201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-03-22T00:17:31-07:00
documentation
PROPIPE
is_lateral_inspection
false