Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 22, 2022, 05:19 AM
  • 15 0100_15 0099_03212022_223623.mp4

Date
03/21/2022
W/O
941303
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00590
PipeID
P11978
Time
10:19 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9930
Sewer Name
15 ABBEY STREET TRUNK
City
LA PUENTE
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
38
Purpose
Routine Assessment
Project
RFIR_WO_941303_TV15204_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0100
Downstream MH
15 0099
Dir. of Survey
Downstream
Length Surveyed
266.4 ft.
Total Length
266.4 ft.
Structural Index
3
Structural Quick
413D
Structural Rating
81
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
81
Pipe schematic from manhole 15 0100 to 15 0099
MH: 15 0100MH: 15 0099downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Begins - 15 01000 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area4.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start50 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"52.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"84.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish97 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start101 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"103.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"138.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish138.6 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start144.7 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Finish149 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"151.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"195.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES199.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"202.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"250.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"253.4 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES253.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"266.4 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK CAPPED266.4 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK266.4 ft. AMH - Downstream Manhole, Survey Ends - 15 0099

Observation photos (5)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    97 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start

    138.6 ft. - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    195.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    253.4 ft. - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

Observations (25)

DistanceCodeObservation
84.6CM
199.9TFC
4.2CM
103.7TFC
138.6CM
0MGOCONNECTION AT THE MH 3 OC'LOCK
195.5FM
50TFC
52.5TFC
250.9TFC
149TF
253.4CL
266.4MGOCONNECTION AT THE MH 3 OC'LOCK CAPPED
151.2TFC
144.7FL
101TFC
253.4TFC
266.4MGOCONNECTION AT THE MH 9 OC'LOCK
266.4AMH15 0099
0AMH15 0100
138.6FL
97CM
0MWL
202.7TFC
0MWM

Properties (7)

additional_info
630074032122201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-03-21T22:19:42-07:00
documentation
PROPIPE
is_lateral_inspection
false