Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 22, 2022, 05:36 AM
  • 15 0099_15 0098_03212022_225418.mp4

Date
03/21/2022
W/O
941303
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00590
PipeID
P11977
Time
10:36 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9930
Sewer Name
15 ABBEY STREET TRUNK
City
LA PUENTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
38
Purpose
Routine Assessment
Project
RFIR_WO_941303_TV15204_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0099
Downstream MH
15 0098
Dir. of Survey
Downstream
Length Surveyed
286.7 ft.
Total Length
286.7 ft.
Structural Index
3
Structural Quick
423H
Structural Rating
143
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
145
Pipe schematic from manhole 15 0099 to 15 0098
MH: 15 0099MH: 15 0098downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 00990 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK CAPPED0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK9.5 ft. CM - Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES34.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"37.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"38.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start51.1 ft. RFB - Roots Fine Barrell, at 01 o'clock85.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"88.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"133.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"136.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"184.8 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"187.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"235.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"238.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"257.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start257.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish266.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish280.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"283.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"286.7 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK CAPPED286.7 ft. AMH - Downstream Manhole, Survey Ends - 15 0098286.7 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK CAPPED

Observation photos (4)

  • Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

    9.5 ft. - Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    38.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Barrell, at 01 o'clock

    51.1 ft. - Roots Fine Barrell, at 01 o'clock

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    257.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (26)

DistanceCodeObservation
257.5FM
0AMH15 0099
0MWL
257.5CM
88.5TFC
235.7TF
133.7TFC
37.4TFC
51.1RFB
0MWM
85.8TFC
238.4TFC
184.8TF
0MGOCONNECTION AT THE MH 3 OC'LOCK CAPPED
34.8TFC
38.8CM
286.7MGOCONNECTION AT THE MH 9 OC'LOCK CAPPED
283.2TFC
286.7AMH15 0098
136.4TFC
280.5TFC
187.4TFC
0MGOCONNECTION AT THE MH 9 OC'LOCK
9.5CM
266.6FM
286.7MGOCONNECTION AT THE MH 3 OC'LOCK CAPPED

Properties (7)

additional_info
630074032122201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-03-21T22:36:30-07:00
documentation
PROPIPE
is_lateral_inspection
false