Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 18, 2022, 06:56 AM
  • C 0561_C 0560_03182022_000922.mp4

Date
03/17/2022
W/O
941898
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00362
PipeID
P04745
Time
11:56 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9925
Sewer Name
C JOINT OUTFALL C - UNIT 4D
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
12
Purpose
Routine Assessment
Project
WO_941898_TV03080_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
21 in.
Upstream MH
C 0561
Downstream MH
C 0560
Dir. of Survey
Downstream
Length Surveyed
419.7 ft.
Total Length
419.7 ft.
Structural Index
2
Structural Quick
3123
Structural Rating
9
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
9
Pipe schematic from manhole C 0561 to C 0560
MH: C 0561MH: C 0560downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - C 05610 ft. MWL - Water Level, 20 %of cross sectional area29.4 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES43.6 ft. CM - Crack Multiple, from 09 to 11 o'clock, within 8 inches of joint: NO55.6 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES308.6 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES419.7 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK CAPPED419.7 ft. AMH - Downstream Manhole, Survey Ends - C 0560

Observation photos (4)

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    29.4 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 11 o'clock, within 8 inches of joint: NO

    43.6 ft. - Crack Multiple, from 09 to 11 o'clock, within 8 inches of joint: NO

  • Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    55.6 ft. - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    308.6 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

Observations (9)

DistanceCodeObservation
308.6CL
29.4CL
55.6CL
419.7MGOCONNECTION AT THE MH 9 OC'LOCK CAPPED
0MWM
43.6CM
419.7AMHC 0560
0AMHC 0561
0MWL

Properties (7)

additional_info
630074031722202
custom_field_three
NO SEVERE DEFECTS
custom_field_two
4
customer
1
datetime
2022-03-17T23:56:23-07:00
documentation
PROPIPE
is_lateral_inspection
false