Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 18, 2022, 08:23 AM
  • C 0558_C 0557_03182022_013832.mp4

Date
03/18/2022
W/O
941898
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00362
PipeID
P04742
Time
1:23 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9925
Sewer Name
C JOINT OUTFALL C - UNIT 4D
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
12
Purpose
Routine Assessment
Project
WO_941898_TV03080_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
15 in.
Upstream MH
C 0558
Downstream MH
C 0557
Dir. of Survey
Downstream
Length Surveyed
396.4 ft.
Total Length
396.4 ft.
Structural Index
2
Structural Quick
423B
Structural Rating
91
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
91
Pipe schematic from manhole C 0558 to C 0557
MH: C 0558MH: C 0557downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - C 05582.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start32.1 ft. FM - Fracture Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES59.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish79.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start87.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish138.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start233.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish268.9 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES316.6 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES351.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES375.1 ft. CM - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES394.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES396.4 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK396.4 ft. AMH - Downstream Manhole, Survey Ends - C 0557396.4 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK

Observation photos (8)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES

    32.1 ft. - Fracture Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    79.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    138.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES

    268.9 ft. - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES

    316.6 ft. - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    351.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    375.1 ft. - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
59.5FL
316.6FC
394.9CM
138.7CL
2.5FL
87.2CL
396.4MGOCONNECTION AT THE MH 3 OC'LOCK
396.4AMHC 0557
396.4MGOCONNECTION AT THE MH 9 OC'LOCK
0MWL
0MWM
32.1FM
351.7FM
233.6CL
0AMHC 0558
375.1CM
79.7CL
268.9FC

Properties (7)

additional_info
630074031722202
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-03-18T01:23:55-07:00
documentation
PROPIPE
is_lateral_inspection
false