Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 5, 2022, 09:55 AM
  • 01 1185_01 1184_04052022_031233.mp4

Date
04/05/2022
W/O
946714
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00225
PipeID
P02039
Time
2:55 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10054
Sewer Name
01 WILCOX AVENUE TRUNK
City
BELL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_946714_TV01257_APR2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
21 in.
Upstream MH
01 1185
Downstream MH
01 1184
Dir. of Survey
Downstream
Length Surveyed
392.4 ft.
Total Length
392.4 ft.
Structural Index
3
Structural Quick
3O00
Structural Rating
234
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
234
Pipe schematic from manhole 01 1185 to 01 1184
MH: 01 1185MH: 01 1184downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 11850 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area3.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.8 ft. MGO - General Observation - MAG COAT6.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"10.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"50.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"54 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"91.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"94.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"127.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"131.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"171.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"199.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"210.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"213.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"253.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"278.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"291.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"324.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"331.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"334.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"345.1 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES388.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish392.4 ft. AMH - Downstream Manhole, Survey Ends - 01 1184392.4 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK392.4 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    345.1 ft. - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES

Observations (28)

DistanceCodeObservation
331.4TF
50.2TF
3.8SAV
213.2TF
392.4AMH01 1184
253.8TF
345.1FL
199.2TFA
127.4TF
388.5SAV
0AMH01 1185
94.6TF
0MWM
171.4TF
91.3TF
324.6TF
0MWL
334.3TF
291.5TF
278.4TF
6.1TF
3.8MGOMAG COAT
392.4MGOCONNECTION AT THE MH 9 OC'LOCK
10.3TF
54TF
392.4MGOCONNECTION AT THE MH 3 OC'LOCK
210.7TF
131.6TF

Properties (7)

additional_info
630074040422202
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-04-05T02:55:52-07:00
documentation
PROPIPE
is_lateral_inspection
false