Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 6, 2022, 11:34 AM
  • 01 1176A_01 1176_04062022_044937.mp4

Date
04/06/2022
W/O
946714
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00225
PipeID
P02029
Time
4:34 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9793
Sewer Name
01 WILCOX AVENUE TRUNK
City
BELL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_946714_TV01257_APR2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
24 in.
Upstream MH
01 1176A
Downstream MH
01 1176
Dir. of Survey
Downstream
Length Surveyed
194.7 ft.
Total Length
194.7 ft.
Structural Index
3
Structural Quick
3G00
Structural Rating
123
O&M Index
2
O&M Quick
2G11
O&M Rating
79
Overall Index
2
Overall Quick
Overall Rating
202
Pipe schematic from manhole 01 1176A to 01 1176
MH: 01 1176AMH: 01 1176downstream0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 1176A2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start7.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES36.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES43 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 4"51 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 4"68.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"94.9 ft. RFJ - Roots Fine Joint, from 10 to 02 o'clock, within 8 inches of joint: YES95.8 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: NO96.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"104.8 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 4"143.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"145.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"181.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES183.7 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 4"192.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish192.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish194 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK194.7 ft. AMH - Downstream Manhole, Survey Ends - 01 1176

Observation photos (7)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    7.8 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    36.6 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 10 to 02 o'clock, within 8 inches of joint: YES

    94.9 ft. - Roots Fine Joint, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: NO

    95.8 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: NO

  • Deposits Attached Grease, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES

    181.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES

Observations (23)

DistanceCodeObservation
194MGOCONNECTION AT THE MH 3 OC'LOCK
0MWM
7.8FL
51TF
104.8TF
181.6DAGS
36.6FL
95.8FL
183.7TFA
145.4TF
192.7SAP
2.1SAP
0MGOCONNECTION AT THE MH 3 OC'LOCK
94.9RFJ
194.7AMH01 1176
96.9TF
143.2TF
43TF
192.7DAGS
2.1DAGS
68.7TF
0MWL
0AMH01 1176A

Properties (7)

additional_info
6300630406222022
custom_field_three
FRACTURES, AGGREGATE PROJECTING
custom_field_two
2
customer
1
datetime
2022-04-06T04:34:17-07:00
documentation
PROPIPE
is_lateral_inspection
false