Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 24, 2022, 05:24 AM
  • 18 1045_18 1044_03232022_224148.mp4

Date
03/23/2022
W/O
947003
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00678
PipeID
P14899
Time
10:24 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9936
Sewer Name
18 LA HABRA HEIGHTS TRUNK, SECTION 2A
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_647003_TV18160_APR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
18 1045
Downstream MH
18 1044
Dir. of Survey
Downstream
Length Surveyed
265.8 ft.
Total Length
265.8 ft.
Structural Index
3
Structural Quick
5142
Structural Rating
157
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
157
Pipe schematic from manhole 18 1045 to 18 1044
MH: 18 1045MH: 18 1044downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 10450.5 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK7.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start97.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"158.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"210.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"248 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start248 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish248 ft. B - Broken, from 08 to 12 o'clock, within 8 inches of joint: YES260 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish265.8 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK265.8 ft. AMH - Downstream Manhole, Survey Ends - 18 1044

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    248 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
265.8MGOCONNECTION AT THE MH 3 OC'LOCK
248FM
248CM
260FM
265.8AMH18 1044
0MWM
158.4TF
0MWL
7.7CM
97.7TF
0.5MGOCONNECTION AT THE MH 3 OC'LOCK
0AMH18 1045
248B
210.1TF

Properties (7)

additional_info
630074032322061
custom_field_three
multiple cracks
custom_field_two
2
customer
1
datetime
2022-03-23T22:24:14-07:00
documentation
PROPIPE
is_lateral_inspection
false