Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 24, 2022, 04:52 AM
  • 18 1041_18 1040_03232022_220537.mp4

Date
03/23/2022
W/O
947003
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00678
PipeID
P14895
Time
9:52 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9936
Sewer Name
18 LA HABRA HEIGHTS TRUNK, SECTION 2A
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_647003_TV18160_APR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
18 1041
Downstream MH
18 1040
Dir. of Survey
Downstream
Length Surveyed
221.3 ft.
Total Length
221.3 ft.
Structural Index
3
Structural Quick
443E
Structural Rating
113
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
113
Pipe schematic from manhole 18 1041 to 18 1040
MH: 18 1041MH: 18 1040downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 10410 ft. MWM - Water Mark, 10 %of cross sectional area4.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start23 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish35.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES48.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"58 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES65.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start79.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"125.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"148.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"183 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"221.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish221.3 ft. AMH - Downstream Manhole, Survey Ends - 18 1040

Observation photos (4)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    35.3 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    58 ft. - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    65.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
0MWL
148.3TF
79.2TF
221.3CM
221.3AMH18 1040
0AMH18 1041
23FM
35.3CL
4.8FM
183TF
125.7TF
0MWM
65.9CM
48.4TF
58CL

Properties (7)

additional_info
630074032322061
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2022-03-23T21:52:04-07:00
documentation
PROPIPE
is_lateral_inspection
false