Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 7, 2022, 09:37 AM
  • C 0711_C JOINT_04072022_025041.mp4

Date
04/07/2022
W/O
946915
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00120
PipeID
P20575
Time
2:37 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K10036
Sewer Name
C JOINT OUTFALL C - UNIT 3A
City
LONG BEACH
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_946915_TV03161_APR2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
72 in.
Width
72 in.
Upstream MH
C 0711
Downstream MH
C JOINT
Dir. of Survey
Downstream
Length Surveyed
91 ft.
Total Length
91 ft.
Structural Index
4
Structural Quick
5B3B
Structural Rating
147
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
151
Pipe schematic from manhole C 0711 to C JOINT
MH: C 0711MH: C JOINTdownstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 55 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - C 07116 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start9.9 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES20.6 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start48.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start88.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish89.2 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish89.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish91 ft. AJB - Junction Box - C JOINT

Observation photos (5)

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES

    6 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES

    9.9 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

    20.6 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    48.8 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
0MWL
9.9SRV
0MWM
91AJBC JOINT
6SRV
88.7SSS
48.8SSS
89.4SAP
6SAP
20.6SRV
89.2SRV
0AMHC 0711

Properties (7)

additional_info
630074040622202
custom_field_three
REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2022-04-07T02:37:37-07:00
documentation
PROPIPE
is_lateral_inspection
false