Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 31, 2022, 05:46 AM
  • 03 0591_03 0590_03302022_225641.mp4

Date
03/30/2022
W/O
946701
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00899
PipeID
P20509
Time
10:46 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9945
Sewer Name
03 DE FOREST AVENUE TRUNK
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_946701_TV03154_APR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
42 in.
Width
42 in.
Upstream MH
03 0591
Downstream MH
03 0590
Dir. of Survey
Downstream
Length Surveyed
148.2 ft.
Total Length
148.2 ft.
Structural Index
3
Structural Quick
4A37
Structural Rating
73
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
77
Pipe schematic from manhole 03 0591 to 03 0590
MH: 03 0591MH: 03 0590downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 03 059113.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start39.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish40.3 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start52.3 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start52.3 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Finish80.2 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish105.8 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 08 o'clock, , within 8 inches of joint: YES106 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start112.5 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Finish112.8 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start137.9 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 08 o'clock, , within 8 inches of joint: YES140.8 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish148.2 ft. AMH - Downstream Manhole, Survey Ends - 03 0590

Observation photos (7)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    13.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start

    40.3 ft. - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    52.3 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 08 o'clock,  , within 8 inches of joint: YES

    105.8 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 08 o'clock, , within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start

    106 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    112.8 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 08 o'clock,  , within 8 inches of joint: YES

    137.9 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 08 o'clock, , within 8 inches of joint: YES

Observations (16)

DistanceCodeObservation
0MWM
148.2AMH03 0590
52.3FM
52.3FL
106CL
0MWL
80.2FM
137.9DAE
40.3FL
105.8DAE
0AMH03 0591
112.8FM
39.5CM
112.5CL
13.4CM
140.8FM

Properties (8)

additional_info
630098033022202
custom_field_three
MULTIPLE CRACKS/FRACTURE'S
custom_field_two
2
customer
1
datetime
2022-03-30T22:46:24-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
35338