Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 18, 2022, 04:25 AM
  • 05 1835_05 1834_03172022_214031.mp4

Date
03/17/2022
W/O
941629
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00492
PipeID
P07057
Time
9:25 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9924
Sewer Name
05 NARBONNE AVENUE CONNECTION TRUNK
City
LOMITA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
36
Purpose
Routine Assessment
Project
WO_941629_TV05375_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1835
Downstream MH
05 1834
Dir. of Survey
Downstream
Length Surveyed
202.8 ft.
Total Length
202.8 ft.
Structural Index
4
Structural Quick
4F31
Structural Rating
135
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
135
Pipe schematic from manhole 05 1835 to 05 1834
MH: 05 1835MH: 05 1834downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Begins - 05 18350 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area18.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES34.4 ft. CM - Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES40.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start57 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"63.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"75.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"84.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6", 6"97 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"103.2 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"121.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"163.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6", 6"169.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"199.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish202.8 ft. AMH - Downstream Manhole, Survey Ends - 05 1834

Observation photos (4)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    18.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES

    34.4 ft. - Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    40.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    103.2 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

Observations (18)

DistanceCodeObservation
34.4CM
121.4TFC
84.8TFA
57TF
103.2TB
97TF
163.9TFA
0MGOCONNECTION AT THE MH 3 OC'LOCK
40.1FM
202.8AMH05 1834
169.8TF
199.7FM
0AMH05 1835
63.4TFC
0MWL
0MWM
18.8FM
75.6TFC

Properties (7)

additional_info
630074031722201
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2022-03-17T21:25:31-07:00
documentation
PROPIPE
is_lateral_inspection
false