Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 10, 2022, 10:41 AM
  • 18 0165_18 0164_03102022_040228.mp4

Date
03/10/2022
W/O
941308
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00695
PipeID
P13988
Time
2:41 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9917
Sewer Name
18 ORR AND DAY ROAD TRUNK
City
NORWALK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
24
Purpose
Routine Assessment
Project
WO_941308_TV18043_MAR2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
18 0164
Downstream MH
18 0165
Dir. of Survey
Upstream
Length Surveyed
501.9 ft.
Total Length
501.9 ft.
Structural Index
3
Structural Quick
513S
Structural Rating
302
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
302
Pipe schematic from manhole 18 0164 to 18 0165
MH: 18 0164MH: 18 0165upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 01650 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK3.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish46.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"100.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"395.6 ft. SRV - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: NO499.7 ft. MGO - General Observation - MAG COAT499.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start501.9 ft. MWL - Water Level, 20 %of cross sectional area501.9 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK501.9 ft. AMH - Downstream Manhole, Survey Begins - 18 0164501.9 ft. MWM - Water Mark, 35 %of cross sectional area

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    2.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: NO

    106.3 ft. - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: NO

Observations (13)

DistanceCodeObservation
401.2TFA
2.2MGOMAG COAT
0MWL
501.9AMH18 0165
2.2SAV
0MGOCONNECTION AT THE MH 3 OC'LOCK
498SAV
0AMH18 0164
501.9MGOCONNECTION AT THE MH 9 OC'LOCK
455TFA
0MWM
501.9MGOCONNECTION AT THE MH 3 OC'LOCK
106.3SRV

Properties (7)

additional_info
630074030922201
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-03-10T02:41:39-08:00
documentation
PROPIPE
is_lateral_inspection
false