Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 8, 2022, 05:13 AM
  • 18 0202_18 0201_03072022_223209.mp4

Date
03/07/2022
W/O
941308
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00695
PipeID
P14027
Time
9:13 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9915
Sewer Name
18 ORR AND DAY ROAD TRUNK
City
SANTA FE SPRINGS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
13
Purpose
Routine Assessment
Project
WO_941308_TV18043_MAR2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
18 0202
Downstream MH
18 0201
Dir. of Survey
Downstream
Length Surveyed
373.8 ft.
Total Length
373.8 ft.
Structural Index
3
Structural Quick
5H3N
Structural Rating
590
O&M Index
2
O&M Quick
412K
O&M Rating
122
Overall Index
3
Overall Quick
Overall Rating
712
Pipe schematic from manhole 18 0202 to 18 0201
MH: 18 0202MH: 18 0201downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 45 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 02022.1 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start76.6 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start114.5 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO138.8 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start252.5 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish269.6 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start371.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish371.4 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish371.4 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish371.4 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish373.8 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK CAPPED373.8 ft. AMH - Downstream Manhole, Survey Ends - 18 0201

Observation photos (5)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO

    114.5 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    138.8 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    269.6 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
2.1SAV
371.4SSS
2.1SSS
114.5SRV
373.8MGOCONNECTION AT THE MH 9 OC'LOCK CAPPED
371.4SRV
76.6DSZ
371.4SAV
138.8SRV
0MWM
371.4DSZ
0MWL
252.5SRV
269.6SRV
0AMH18 0202
373.8AMH18 0201

Properties (7)

additional_info
630074030722201
custom_field_three
REINFORCEMENT VISIBLE/SPALLING/AGGREGATE VISIBLE
custom_field_two
2
customer
1
datetime
2022-03-07T21:13:48-08:00
documentation
PROPIPE
is_lateral_inspection
false