Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 15, 2022, 09:32 AM
  • 18 0127_18 0126_03152022_024542.mp4

Date
03/15/2022
W/O
941308
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00695
PipeID
P13948
Time
2:32 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9920
Sewer Name
18 ORR AND DAY ROAD TRUNK
City
NORWALK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
29
Purpose
Routine Assessment
Project
WO_941308_TV18043_MAR2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
18 0127
Downstream MH
18 0126
Dir. of Survey
Downstream
Length Surveyed
395.9 ft.
Total Length
395.9 ft.
Structural Index
3
Structural Quick
543O
Structural Rating
257
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
257
Pipe schematic from manhole 18 0127 to 18 0126
MH: 18 0127MH: 18 0126downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 01270 ft. MWM - Water Mark, 35 %of cross sectional area4.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.6 ft. MGO - General Observation - MAG COAT28.7 ft. SAP - Surface Aggregate Projecting, from 03 to 04 o'clock, within 8 inches of joint: NO34.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish34.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start200.2 ft. SRV - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO290.2 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO338.9 ft. SRV - Surface Reinforcement Visible, from 01 to 04 o'clock, within 8 inches of joint: NO369.8 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO392.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish395.9 ft. AMH - Downstream Manhole, Survey Ends - 18 0126

Observation photos (7)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 03 to 04 o'clock, within 8 inches of joint: NO

    28.7 ft. - Surface Aggregate Projecting, from 03 to 04 o'clock, within 8 inches of joint: NO

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    34.4 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO

    200.2 ft. - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO

    290.2 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 01 to 04 o'clock, within 8 inches of joint: NO

    338.9 ft. - Surface Reinforcement Visible, from 01 to 04 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO

    369.8 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO

Observations (14)

DistanceCodeObservation
0MWL
34.4SAP
395.9AMH18 0126
392.9SAP
200.2SRV
290.2SRV
4.6SAV
28.7SAP
338.9SRV
34.3SAV
0AMH18 0127
0MWM
4.6MGOMAG COAT
369.8SRV

Properties (7)

additional_info
630074031422201
custom_field_three
AGGREGATE PROJECTING/REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2022-03-15T02:32:03-07:00
documentation
PROPIPE
is_lateral_inspection
false