Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 14, 2022, 10:33 AM
  • 18 0150_18 0149_03142022_035146.mp4

Date
03/14/2022
W/O
941308
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00695
PipeID
P13972
Time
3:33 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9919
Sewer Name
18 ORR AND DAY ROAD TRUNK
City
NORWALK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
24
Purpose
Routine Assessment
Project
WO_941308_TV18043_MAR2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
18 0150
Downstream MH
18 0149
Dir. of Survey
Downstream
Length Surveyed
352.6 ft.
Total Length
352.6 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
210
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
210
Pipe schematic from manhole 18 0150 to 18 0149
MH: 18 0150MH: 18 0149downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 01502.2 ft. MGO - General Observation - MAG COAT2.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start30.9 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"65.4 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"105 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"150.1 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"186.2 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"198.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"205.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"266 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"310 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"315.5 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"350 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish352.6 ft. AMH - Downstream Manhole, Survey Ends - 18 0149352.6 ft. MGO - General Observation, 6" - CONNECTION AT THE MH 9 OC'LOCK352.6 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK

Observation photos (7)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"

    30.9 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"

    65.4 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"

    105 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    150.1 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    186.2 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    198.4 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (20)

DistanceCodeObservation
315.5TFA
30.9TB
0MWM
352.6AMH18 0149
2.2MGOMAG COAT
198.4TB
150.1TB
352.6MGOCONNECTION AT THE MH 9 OC'LOCK
352.6MGOCONNECTION AT THE MH 3 OC'LOCK
105TB
2.2SAV
65.4TB
350SAV
0MGOCONNECTION AT THE MH 9 OC'LOCK
0MWL
0AMH18 0150
205.7TF
266TFA
310TB
186.2TBA

Properties (7)

additional_info
630074031422061
custom_field_three
NO SEVERE DEFECTS
custom_field_two
4
customer
1
datetime
2022-03-14T03:33:07-07:00
documentation
PROPIPE
is_lateral_inspection
false