Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 14, 2022, 10:52 AM
  • 18 0149_18 0148_03142022_040312.mp4

Date
03/14/2022
W/O
941308
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00695
PipeID
P13971
Time
3:52 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9919
Sewer Name
18 ORR AND DAY ROAD TRUNK
City
NORWALK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
29
Purpose
Routine Assessment
Project
WO_941308_TV18043_MAR2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
18 0149
Downstream MH
18 0148
Dir. of Survey
Downstream
Length Surveyed
405 ft.
Total Length
405 ft.
Structural Index
3
Structural Quick
3O00
Structural Rating
240
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
240
Pipe schematic from manhole 18 0149 to 18 0148
MH: 18 0149MH: 18 0148downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 01490 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK2.6 ft. MGO - General Observation - MAG COAT2.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start36 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"56 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"95.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"163.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"208.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"251.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"300.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"345.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"348.7 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"405 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK405 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish405 ft. AMH - Downstream Manhole, Survey Ends - 18 0148

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    348.7 ft. - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (19)

DistanceCodeObservation
348.7TBA
208.8TF
163.5TF
405MGOCONNECTION AT THE MH 9 OC'LOCK
251.5TF
0AMH18 0149
0MWM
36TF
2.6MGOMAG COAT
95.7TF
56TF
405SAV
0MWL
300.9TF
2.6SAV
0MGOCONNECTION AT THE MH 9 OC'LOCK
405AMH18 0148
345.5TF
0MGOCONNECTION AT THE MH 3 OC'LOCK

Properties (7)

additional_info
630074031422061
custom_field_three
NO SEVERE DEFECTS
custom_field_two
4
customer
1
datetime
2022-03-14T03:52:01-07:00
documentation
PROPIPE
is_lateral_inspection
false