Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 14, 2022, 11:03 AM
  • 18 0148_18 0147_03142022_041341.mp4

Date
03/14/2022
W/O
941308
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00695
PipeID
P13970
Time
4:03 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9919
Sewer Name
18 ORR AND DAY ROAD TRUNK
City
NORWALK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
29
Purpose
Routine Assessment
Project
WO_941308_TV18043_MAR2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
18 0148
Downstream MH
18 0147
Dir. of Survey
Downstream
Length Surveyed
192.3 ft.
Total Length
192.3 ft.
Structural Index
3
Structural Quick
3F00
Structural Rating
111
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
111
Pipe schematic from manhole 18 0148 to 18 0147
MH: 18 0148MH: 18 0147downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Begins - 18 01480 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3 ft. MGO - General Observation - MAG COAT46.7 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"101.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"190.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish192.3 ft. MGO - General Observation - CONNECTION AT THE MH 12 OC'LOCK192.3 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK192.3 ft. AMH - Downstream Manhole, Survey Ends - 18 0147

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    46.7 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (12)

DistanceCodeObservation
0MGOCONNECTION AT THE MH 9 OC'LOCK
192.3MGOCONNECTION AT THE MH 12 OC'LOCK
0AMH18 0148
190.2SAV
46.7TB
0MWL
101.8TF
3SAV
192.3MGOCONNECTION AT THE MH 3 OC'LOCK
3MGOMAG COAT
0MWM
192.3AMH18 0147

Properties (7)

additional_info
630074031422061
custom_field_three
NO SEVERE DEFECTS
custom_field_two
4
customer
1
datetime
2022-03-14T04:03:28-07:00
documentation
PROPIPE
is_lateral_inspection
false