Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 15, 2022, 04:31 AM
  • 18 0146_18 0145_03142022_214057.mp4

Date
03/14/2022
W/O
941308
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00695
PipeID
P13968
Time
9:31 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9920
Sewer Name
18 ORR AND DAY ROAD TRUNK
City
NORWALK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
29
Purpose
Routine Assessment
Project
WO_941308_TV18043_MAR2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
18 0146
Downstream MH
18 0145
Dir. of Survey
Downstream
Length Surveyed
238.9 ft.
Total Length
238.9 ft.
Structural Index
3
Structural Quick
513H
Structural Rating
146
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
146
Pipe schematic from manhole 18 0146 to 18 0145
MH: 18 0146MH: 18 0145downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 01462.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.2 ft. MGO - General Observation - MAG COAT20.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"66.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"116.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"170.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"193 ft. SRV - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO214.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"235.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish238.9 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK238.9 ft. AMH - Downstream Manhole, Survey Ends - 18 0145

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO

    193 ft. - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO

Observations (15)

DistanceCodeObservation
2.2SAV
193SRV
238.9MGOCONNECTION AT THE MH 9 OC'LOCK
0MGOCONNECTION AT THE MH 9 OC'LOCK
66.3TF
235.6SAV
116.6TF
170.7TF
0MWL
2.2MGOMAG COAT
214.4TF
238.9AMH18 0145
20.9TF
0MWM
0AMH18 0146

Properties (7)

additional_info
630074031422201
custom_field_three
AGGREGATE VISIBLE/REINFORCEMENT VISIBLE
custom_field_two
3
customer
1
datetime
2022-03-14T21:31:28-07:00
documentation
PROPIPE
is_lateral_inspection
false