Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 15, 2022, 06:24 AM
  • C 0387_C 0386_03142022_235522.mp4

Date
03/14/2022
W/O
941947
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00142
PipeID
P09851
Time
11:24 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9961
Sewer Name
C JOINT OUTFALL C - UNIT 8D
City
LAKEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_941947_TV19067_MAR2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
114 in.
Upstream MH
C 0387
Downstream MH
C 0386
Dir. of Survey
Downstream
Length Surveyed
531.2 ft.
Total Length
531.2 ft.
Structural Index
3
Structural Quick
5N3T
Structural Rating
900
O&M Index
4
O&M Quick
5742
O&M Rating
51
Overall Index
3
Overall Quick
Overall Rating
951
Pipe schematic from manhole C 0387 to C 0386
MH: C 0387MH: C 0386downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - C 03870 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. MGO - General Observation - MAG COATING2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7 ft. IG - Infiltration Gusher, at 02 o'clock, within 8 inches of joint: YES11 ft. IG - Infiltration Gusher, at 01 o'clock, within 8 inches of joint: YES35.2 ft. ID - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES46.6 ft. IG - Infiltration Gusher, at 03 o'clock, within 8 inches of joint: YES75.7 ft. IG - Infiltration Gusher, at 04 o'clock, within 8 inches of joint: YES127.4 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: YES, 12"243.5 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish358.8 ft. ID - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES400.3 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start415.4 ft. IG - Infiltration Gusher, at 04 o'clock, within 8 inches of joint: NO440.4 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 12"447.3 ft. IG - Infiltration Gusher, at 04 o'clock, within 8 inches of joint: NO479.2 ft. IS - Infiltration Stain, from 08 to 12 o'clock, within 8 inches of joint: YES506.3 ft. LL - Alignment Left, 25 %506.6 ft. IS - Infiltration Stain, from 12 to 04 o'clock, within 8 inches of joint: YES518 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 04 o'clock, , within 8 inches of joint: NO518.1 ft. IG - Infiltration Gusher, at 08 o'clock, within 8 inches of joint: YES518.1 ft. LR - Alignment Right, 25 %523.5 ft. IS - Infiltration Stain, from 08 to 12 o'clock, within 8 inches of joint: YES531.2 ft. MGO - General Observation - GIS CALLS FOR 530'531.2 ft. AMH - Downstream Manhole, Survey Ends - C 0386531.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish531.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish531.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (21)

  • General Observation - MAG COATING

    2 ft. - General Observation - MAG COATING

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.1 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Gusher, at 02 o'clock, within 8 inches of joint: YES

    7 ft. - Infiltration Gusher, at 02 o'clock, within 8 inches of joint: YES

  • Infiltration Gusher, at 01 o'clock, within 8 inches of joint: YES

    11 ft. - Infiltration Gusher, at 01 o'clock, within 8 inches of joint: YES

  • Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

    35.2 ft. - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

  • Infiltration Gusher, at 03 o'clock, within 8 inches of joint: YES

    46.6 ft. - Infiltration Gusher, at 03 o'clock, within 8 inches of joint: YES

  • Infiltration Gusher, at 04 o'clock, within 8 inches of joint: YES

    75.7 ft. - Infiltration Gusher, at 04 o'clock, within 8 inches of joint: YES

  • Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: YES, 12"

    127.4 ft. - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: YES, 12"

  • Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

    358.8 ft. - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    400.3 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Gusher, at 04 o'clock, within 8 inches of joint: NO

    415.4 ft. - Infiltration Gusher, at 04 o'clock, within 8 inches of joint: NO

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 12"

    440.4 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 12"

  • Infiltration Gusher, at 04 o'clock, within 8 inches of joint: NO

    447.3 ft. - Infiltration Gusher, at 04 o'clock, within 8 inches of joint: NO

  • Infiltration Stain, from 08 to 12 o'clock, within 8 inches of joint: YES

    479.2 ft. - Infiltration Stain, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Alignment Left, 25 %

    506.3 ft. - Alignment Left, 25 %

  • Infiltration Stain, from 12 to 04 o'clock, within 8 inches of joint: YES

    506.6 ft. - Infiltration Stain, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Infiltration Gusher, at 08 o'clock, within 8 inches of joint: YES

    518.1 ft. - Infiltration Gusher, at 08 o'clock, within 8 inches of joint: YES

  • Alignment Right, 25 %

    518.1 ft. - Alignment Right, 25 %

  • Infiltration Stain, from 08 to 12 o'clock, within 8 inches of joint: YES

    523.5 ft. - Infiltration Stain, from 08 to 12 o'clock, within 8 inches of joint: YES

Observations (31)

DistanceCodeObservation
531.2MGOGIS CALLS FOR 530'
523.5IS
506.3LL
531.2AMHC 0386
0MWL
46.6IG
127.4TBA
0AMHC 0387
518.1IG
2MGOMAG COATING
2SSS
506.6IS
447.3IG
243.5SRV
518DAGS
2SAP
35.2ID
358.8ID
11IG
479.2IS
415.4IG
531.2SSS
518.1LR
4.1SRV
400.3SRV
0MWM
7IG
440.4TB
75.7IG
531.2SRV
531.2SAP

Properties (8)

additional_info
630098031422201
custom_field_three
INFILTRATION, REINFORCEMENT VISBLE
custom_field_two
1
customer
1
datetime
2022-03-14T23:24:07-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
26643