Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 15, 2022, 06:57 AM
  • C 0386_C 0385_03152022_001541.mp4

Date
03/14/2022
W/O
941947
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00142
PipeID
P09850
Time
11:57 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9961
Sewer Name
C JOINT OUTFALL C - UNIT 8D
City
LAKEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_941947_TV19067_MAR2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
114 in.
Upstream MH
C 0386
Downstream MH
C 0385
Dir. of Survey
Downstream
Length Surveyed
413.8 ft.
Total Length
413.8 ft.
Structural Index
3
Structural Quick
5L3O
Structural Rating
730
O&M Index
3
O&M Quick
3200
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
736
Pipe schematic from manhole C 0386 to C 0385
MH: C 0386MH: C 0385downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - C 03860 ft. MWL - Water Level, 15 %of cross sectional area2.8 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES2.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start9.9 ft. IS - Infiltration Stain, from 08 to 11 o'clock, within 8 inches of joint: YES30.2 ft. IS - Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES71.8 ft. ID - Infiltration Dripper, at 11 o'clock, within 8 inches of joint: YES71.8 ft. IS - Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES72.3 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 12"94.1 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 10"100.8 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start191.9 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 12"216.3 ft. ID - Infiltration Dripper, at 01 o'clock, within 8 inches of joint: YES413.8 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish413.8 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK413.8 ft. AMH - Downstream Manhole, Survey Ends - C 0385413.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish413.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (12)

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    2.8 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Stain, from 08 to 11 o'clock, within 8 inches of joint: YES

    9.9 ft. - Infiltration Stain, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES

    30.2 ft. - Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Infiltration Dripper, at 11 o'clock, within 8 inches of joint: YES

    71.8 ft. - Infiltration Dripper, at 11 o'clock, within 8 inches of joint: YES

  • Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES

    71.8 ft. - Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 12"

    72.3 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 12"

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 10"

    94.1 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 10"

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    100.8 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 12"

    191.9 ft. - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 12"

  • Infiltration Dripper, at 01 o'clock, within 8 inches of joint: YES

    216.3 ft. - Infiltration Dripper, at 01 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
413.8SRV
71.8ID
2.8SRV
0MWM
413.8MGOCONNECTION AT MH 9 O'CLOCK
94.1TB
413.8AMHC 0385
30.2IS
71.8IS
2.8SSS
413.8SAP
2.8SAP
413.8SSS
0AMHC 0386
216.3ID
9.9IS
0MWL
100.8SRV
191.9TBA
72.3TBA

Properties (8)

additional_info
630098031422201
custom_field_three
INFILTRATION, REINFORCEMENT VISBLE
custom_field_two
1
customer
1
datetime
2022-03-14T23:57:04-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
26643