Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 15, 2022, 08:31 AM
  • C 0383_C 0382_03152022_014853.mp4

Date
03/15/2022
W/O
941947
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00142
PipeID
P09847
Time
1:31 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9961
Sewer Name
C JOINT OUTFALL C - UNIT 8D
City
LAKEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_941947_TV19067_MAR2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
78 in.
Upstream MH
C 0383
Downstream MH
C 0382
Dir. of Survey
Downstream
Length Surveyed
361.1 ft.
Total Length
361.1 ft.
Structural Index
3
Structural Quick
5L3M
Structural Rating
677
O&M Index
5
O&M Quick
5331
O&M Rating
18
Overall Index
3
Overall Quick
Overall Rating
695
Pipe schematic from manhole C 0383 to C 0382
MH: C 0383MH: C 0382downstream0 ft. AMH - Upstream Manhole, Survey Begins - C 03830 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. MGO - General Observation - MAG COATING2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start18.8 ft. IG - Infiltration Gusher, at 03 o'clock, within 8 inches of joint: YES18.8 ft. IS - Infiltration Stain, from 09 to 04 o'clock, within 8 inches of joint: YES26.8 ft. IG - Infiltration Gusher, at 11 o'clock, within 8 inches of joint: YES41.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start52.3 ft. IS - Infiltration Stain, from 08 to 10 o'clock, within 8 inches of joint: YES214.2 ft. IS - Infiltration Stain, from 08 to 11 o'clock, within 8 inches of joint: YES235.9 ft. IG - Infiltration Gusher, at 04 o'clock, within 8 inches of joint: YES293.1 ft. ID - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES342.9 ft. IS - Infiltration Stain, from 10 to 04 o'clock, within 8 inches of joint: YES361.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish361.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish361.1 ft. AMH - Downstream Manhole, Survey Ends - C 0382361.1 ft. MGO - General Observation - GIS CALLS FOR 360'361.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish361.1 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (12)

  • General Observation - MAG COATING

    2 ft. - General Observation - MAG COATING

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Gusher, at 03 o'clock, within 8 inches of joint: YES

    18.8 ft. - Infiltration Gusher, at 03 o'clock, within 8 inches of joint: YES

  • Infiltration Stain, from 09 to 04 o'clock, within 8 inches of joint: YES

    18.8 ft. - Infiltration Stain, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Infiltration Gusher, at 11 o'clock, within 8 inches of joint: YES

    26.8 ft. - Infiltration Gusher, at 11 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    41.1 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Stain, from 08 to 10 o'clock, within 8 inches of joint: YES

    52.3 ft. - Infiltration Stain, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Infiltration Stain, from 08 to 11 o'clock, within 8 inches of joint: YES

    214.2 ft. - Infiltration Stain, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Infiltration Gusher, at 04 o'clock, within 8 inches of joint: YES

    235.9 ft. - Infiltration Gusher, at 04 o'clock, within 8 inches of joint: YES

  • Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

    293.1 ft. - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

  • Infiltration Stain, from 10 to 04 o'clock, within 8 inches of joint: YES

    342.9 ft. - Infiltration Stain, from 10 to 04 o'clock, within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
361.1SSS
361.1SAP
2MGOMAG COATING
0AMHC 0383
361.1AMHC 0382
2SSS
18.8IG
361.1MGOGIS CALLS FOR 360'
7SAP
0MWM
361.1SRV
293.1ID
361.1MGOCONNECTION AT MH 9 O'CLOCK
52.3IS
18.8IS
235.9IG
214.2IS
342.9IS
0MWL
41.1SRV
26.8IG

Properties (8)

additional_info
630098031422201
custom_field_three
INFILTRATION, REINFORCEMENT VISIBLE
custom_field_two
1
customer
1
datetime
2022-03-15T01:31:22-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
26643