Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 17, 2022, 08:58 AM
  • 01 0038A_01 0038_03172022_020809.mp4

Date
03/17/2022
W/O
941336
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00209
PipeID
P00699
Time
1:58 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10011
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_941336_TV01255_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
27 in.
Upstream MH
01 0038
Downstream MH
01 0038A
Dir. of Survey
Upstream
Length Surveyed
118.8 ft.
Total Length
118.8 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 01 0038 to 01 0038A
MH: 01 0038MH: 01 0038Aupstream0 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish0 ft. MSA - Survey Abandoned - AT DEBRIS. REVERSAL COMPLETE.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"3.4 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"26.9 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6"31.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"50.1 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - debris55.5 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"60.8 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"98.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"101 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"116.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start116.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start118.8 ft. AMH - Downstream Manhole, Survey Begins - 01 0038118.8 ft. MWM - Water Mark, 15 %of cross sectional area118.8 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
118.8CM
87.7TFC
117.8TFC
118.8DSZ
2CM
115.4TF
118.8DAGS
118.8MSAAT DEBRIS. REVERSAL COMPLETE.
0AMH01 0038
17.8TF
0MWM
91.9TB
58TB
0MWL
20TFC
68.7DSZdebris
2DAGS
63.3TF

Properties (7)

additional_info
630138031622201
custom_field_three
CRACKS/DEBRIS
custom_field_two
2
customer
1
datetime
2022-03-17T01:58:35-07:00
documentation
PRO PIPE
is_lateral_inspection
false