Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 1, 2022, 09:28 AM
  • 01 0064_01 0063_03012022_025140.mp4

Date
03/01/2022
W/O
941336
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00209
PipeID
P00733
Time
1:28 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9888
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
FLORENCE-FIRESTONE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_941336_TV01255_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0064
Downstream MH
01 0063
Dir. of Survey
Downstream
Length Surveyed
365.8 ft.
Total Length
365.8 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
3
O&M Quick
4138
O&M Rating
32
Overall Index
3
Overall Quick
Overall Rating
35
Pipe schematic from manhole 01 0064 to 01 0063
MH: 01 0064MH: 01 0063downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 00640 ft. MGO - General Observation - COCKROACHES IN MH0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start5.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start12.7 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"14.9 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"14.9 ft. RMC - Roots Medium Connection, from 07 to 12 o'clock, 20 %, within 8 inches of joint: YES36.2 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"59 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"59 ft. RFC - Roots Fine Connection, from 08 to 11 o'clock70.9 ft. RFC - Roots Fine Connection, from 01 to 04 o'clock70.9 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"97.5 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"97.5 ft. RMC - Roots Medium Connection, from 08 to 11 o'clock, 15 %, within 8 inches of joint: YES135.8 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"135.8 ft. RMC - Roots Medium Connection, from 12 to 04 o'clock, 25 %, within 8 inches of joint: YES139.1 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"147 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"147 ft. RMC - Roots Medium Connection, from 08 to 11 o'clock, 20 %, within 8 inches of joint: YES183.6 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"186.1 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"219.1 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"219.1 ft. RMC - Roots Medium Connection, from 01 to 04 o'clock, 15 %, within 8 inches of joint: YES233.2 ft. RMC - Roots Medium Connection, from 08 to 11 o'clock, 15 %, within 8 inches of joint: YES233.2 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"238.1 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"238.1 ft. RMC - Roots Medium Connection, from 01 to 05 o'clock, 25 %, within 8 inches of joint: YES267.5 ft. RMC - Roots Medium Connection, from 08 to 11 o'clock, 25 %, within 8 inches of joint: YES267.5 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"292.3 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"340.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"342.5 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"363.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish363.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish365.8 ft. AMH - Downstream Manhole, Survey Ends - 01 0063365.8 ft. MGO - General Observation - COCKROACHES IN MH365.8 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (14)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    5.2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Connection, from 07 to 12 o'clock, 20 %, within 8 inches of joint: YES

    14.9 ft. - Roots Medium Connection, from 07 to 12 o'clock, 20 %, within 8 inches of joint: YES

  • Roots Fine Connection, from 08 to 11 o'clock

    59 ft. - Roots Fine Connection, from 08 to 11 o'clock

  • Roots Fine Connection, from 01 to 04 o'clock

    70.9 ft. - Roots Fine Connection, from 01 to 04 o'clock

  • Roots Medium Connection, from 08 to 11 o'clock, 15 %, within 8 inches of joint: YES

    97.5 ft. - Roots Medium Connection, from 08 to 11 o'clock, 15 %, within 8 inches of joint: YES

  • Roots Medium Connection, from 12 to 04 o'clock, 25 %, within 8 inches of joint: YES

    135.8 ft. - Roots Medium Connection, from 12 to 04 o'clock, 25 %, within 8 inches of joint: YES

  • Roots Medium Connection, from 08 to 11 o'clock, 20 %, within 8 inches of joint: YES

    147 ft. - Roots Medium Connection, from 08 to 11 o'clock, 20 %, within 8 inches of joint: YES

  • Roots Medium Connection, from 01 to 04 o'clock, 15 %, within 8 inches of joint: YES

    219.1 ft. - Roots Medium Connection, from 01 to 04 o'clock, 15 %, within 8 inches of joint: YES

  • Roots Medium Connection, from 08 to 11 o'clock, 15 %, within 8 inches of joint: YES

    233.2 ft. - Roots Medium Connection, from 08 to 11 o'clock, 15 %, within 8 inches of joint: YES

  • Roots Medium Connection, from 01 to 05 o'clock, 25 %, within 8 inches of joint: YES

    238.1 ft. - Roots Medium Connection, from 01 to 05 o'clock, 25 %, within 8 inches of joint: YES

  • Roots Medium Connection, from 08 to 11 o'clock, 25 %, within 8 inches of joint: YES

    267.5 ft. - Roots Medium Connection, from 08 to 11 o'clock, 25 %, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MH

    365.8 ft. - General Observation - COCKROACHES IN MH

Observations (39)

DistanceCodeObservation
238.1TFA
14.9TFA
363.5CM
36.2TFA
59TFA
139.1TF
5.2CM
219.1TFA
238.1RMC
12.7TFA
14.9RMC
292.3TFA
70.9RFC
365.8AMH01 0063
0AMH01 0064
183.6TFA
147TFA
365.8MGOCOCKROACHES IN MH
186.1TFA
135.8TFA
147RMC
97.5TFA
365.8MGOCONNECTION AT MH 3 O'CLOCK
219.1RMC
363.5DAGS
0MGOCOCKROACHES IN MH
0MWL
135.8RMC
2DAGS
340.7TFC
0MWM
70.9TFA
233.2RMC
267.5RMC
233.2TFA
97.5RMC
267.5TFA
59RFC
342.5TFA

Properties (7)

additional_info
630138022822201
custom_field_three
MULTIPLE CRACKS/ROOTS
custom_field_two
2
customer
1
datetime
2022-03-01T01:28:25-08:00
documentation
PRO PIPE
is_lateral_inspection
false