Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 1, 2022, 11:31 AM
  • 01 0060_01 0059_03012022_044808.mp4

Date
03/01/2022
W/O
941336
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00209
PipeID
P00729
Time
3:31 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9888
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
FLORENCE-FIRESTONE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_941336_TV01255_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
01 0059
Downstream MH
01 0060
Dir. of Survey
Upstream
Length Surveyed
338.2 ft.
Total Length
338.2 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
3
O&M Quick
4131
O&M Rating
9
Overall Index
3
Overall Quick
Overall Rating
12
Pipe schematic from manhole 01 0059 to 01 0060
MH: 01 0059MH: 01 0060upstream0 ft. AMH - Upstream Manhole, Survey Ends - 01 00600 ft. MGO - General Observation - COCKROACHES IN MH3.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish3.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish13.1 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"15.4 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"15.4 ft. RMC - Roots Medium Connection, from 01 to 05 o'clock, 15 %, within 8 inches of joint: YES51.2 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"54 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"69.2 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"102.5 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"135.5 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"140.3 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"155.4 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"172.9 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"182.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"206.5 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"227.8 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"269.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"271.1 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"312.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"332.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start336.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start338.2 ft. MWL - Water Level, 25 %of cross sectional area338.2 ft. MGO - General Observation - COCKROACHES IN MH338.2 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK338.2 ft. AMH - Downstream Manhole, Survey Begins - 01 0059338.2 ft. MWM - Water Mark, 60 %of cross sectional area

Observation photos (5)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    5.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Connection, from 01 to 05 o'clock, 15 %, within 8 inches of joint: YES

    322.8 ft. - Roots Medium Connection, from 01 to 05 o'clock, 15 %, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MH

    338.2 ft. - General Observation - COCKROACHES IN MH

Observations (28)

DistanceCodeObservation
197.9TFA
322.8TFA
165.3TBA
67.1TFC
338.2AMH01 0060
155.3TFC
0MWL
0MGOCOCKROACHES IN MH
110.4TFA
69.1TFC
287TFA
26.1TFC
335.1DAGS
235.7TFA
335.1CM
131.7TFA
182.8TFA
325.1TFA
2DAGS
0MGOCONNECTION AT MH 9 O'CLOCK
322.8RMC
0AMH01 0059
269TF
338.2MGOCOCKROACHES IN MH
0MWM
202.7TFA
284.2TFA
5.4CM

Properties (7)

additional_info
630138022822201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2022-03-01T03:31:43-08:00
documentation
PRO PIPE
is_lateral_inspection
false