Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 16, 2022, 09:29 AM
  • 01 0049_01 0048A_03162022_023950.mp4

Date
03/16/2022
W/O
941336
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00209
PipeID
P00714
Time
2:29 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10010
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_941336_TV01255_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
01 0049
Downstream MH
01 0048A
Dir. of Survey
Downstream
Length Surveyed
135 ft.
Total Length
135 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 01 0049 to 01 0048A
MH: 01 0049MH: 01 0048Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 00490 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MH2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start53.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"56.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"102.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"105.2 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"133 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish133 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish135 ft. AMH - Downstream Manhole, Survey Ends - 01 0048A135 ft. MGO - General Observation - CONNECTION AT MH 3, 9 O'CLOCK135 ft. MGO - General Observation - COCKROACHES IN MH

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    135 ft. - General Observation - COCKROACHES IN MH

Observations (15)

DistanceCodeObservation
135AMH01 0048A
2DAGS
53.8TFC
0AMH01 0049
133CM
102.3TFC
105.2TFC
135MGOCONNECTION AT MH 3, 9 O'CLOCK
133DAGS
0MWL
4.5CM
56.5TFC
0MWM
135MGOCOCKROACHES IN MH
0MGOCOCKROACHES IN MH

Properties (7)

additional_info
630138031522201
custom_field_three
MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2022-03-16T02:29:20-07:00
documentation
PRO PIPE
is_lateral_inspection
false