Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 17, 2022, 06:24 AM
  • 01 0040_01 0039A_03162022_233812.mp4

Date
03/16/2022
W/O
941336
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00209
PipeID
P25568
Time
11:24 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10011
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_941336_TV01255_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
01 0040
Downstream MH
01 0039A
Dir. of Survey
Downstream
Length Surveyed
282.3 ft.
Total Length
282.3 ft.
Structural Index
3
Structural Quick
3J21
Structural Rating
164
O&M Index
2
O&M Quick
2J00
O&M Rating
112
Overall Index
2
Overall Quick
Overall Rating
276
Pipe schematic from manhole 01 0040 to 01 0039A
MH: 01 0040MH: 01 0039Adownstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 00402 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start9.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start33.1 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: NO44.4 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"50.6 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"93.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"99.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"145.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"151.6 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"194.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"199.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"246.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"251.6 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"279.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish279.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish282.3 ft. AMH - Downstream Manhole, Survey Ends - 01 0039A282.3 ft. MGO - General Observation - COCKROACHES IN MH282.3 ft. MGO - General Observation - CONNECTION AT MH 3, 9 O'CLOCK

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    9.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    282.3 ft. - General Observation - COCKROACHES IN MH

Observations (21)

DistanceCodeObservation
33.1FC
282.3AMH01 0039A
279.9CM
0MWL
251.6TFC
9.2CM
2DAGS
151.6TFC
282.3MGOCOCKROACHES IN MH
279.9DAGS
145.5TFC
199.8TFC
194.5TFC
0MWM
93.7TFC
50.6TFC
0AMH01 0040
44.4TF
282.3MGOCONNECTION AT MH 3, 9 O'CLOCK
99.4TFC
246.3TFC

Properties (7)

additional_info
630138031622201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-03-16T23:24:56-07:00
documentation
PRO PIPE
is_lateral_inspection
false