Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 17, 2022, 06:14 AM
  • 01 0040A_01 0040_03162022_232441.mp4

Date
03/16/2022
W/O
941336
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00209
PipeID
P20032
Time
11:14 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10011
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_941336_TV01255_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
01 0040A
Downstream MH
01 0040
Dir. of Survey
Downstream
Length Surveyed
279.6 ft.
Total Length
279.6 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 01 0040A to 01 0040
MH: 01 0040AMH: 01 0040downstream0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 0040A2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start68 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"117.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"132 ft. RFJ - Roots Fine Joint, at 02 o'clock, within 8 inches of joint: YES170.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"213.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"261.6 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"263.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"277.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish277.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish279.6 ft. AMH - Downstream Manhole, Survey Ends - 01 0040

Observation photos (4)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, at 02 o'clock, within 8 inches of joint: YES

    132 ft. - Roots Fine Joint, at 02 o'clock, within 8 inches of joint: YES

Observations (17)

DistanceCodeObservation
170.9TF
68TF
279.6AMH01 0040
0MGOCOCKROACHES IN MH
2DAGS
0MGOCONNECTION AT MH 9 O'CLOCK
132RFJ
261.6TBA
0MWL
0MWM
0AMH01 0040A
263.5TF
277.6DAGS
4.5CM
117.8TF
277.6CM
213.7TF

Properties (7)

additional_info
630138031622201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-03-16T23:14:27-07:00
documentation
PRO PIPE
is_lateral_inspection
false