Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 28, 2022, 10:32 AM
  • 01 0085_01 0084_02282022_034519.mp4

Date
02/28/2022
W/O
941336
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00209
PipeID
P00754
Time
2:32 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9887
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
FLORENCE-GRAHAM
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_941336_TV01255_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0084
Downstream MH
01 0085
Dir. of Survey
Upstream
Length Surveyed
282.4 ft.
Total Length
282.4 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2211
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
8
Pipe schematic from manhole 01 0084 to 01 0085
MH: 01 0084MH: 01 0085upstream0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. AMH - Upstream Manhole, Survey Ends - 01 00850 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK2.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish2.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish48.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"103.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"136.8 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"144.9 ft. RPZ - Repair Other, within 8 inches of joint: NO - CONCRETE PATCH150 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 06 o'clock, , within 8 inches of joint: YES156 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"193.2 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"239.5 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"243.2 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"245.3 ft. RFJ - Roots Fine Joint, from 02 to 03 o'clock, within 8 inches of joint: YES280.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start280.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start282.4 ft. MWL - Water Level, 20 %of cross sectional area282.4 ft. MWM - Water Mark, 40 %of cross sectional area282.4 ft. AMH - Downstream Manhole, Survey Ends - 01 0084

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 02 to 03 o'clock, within 8 inches of joint: YES

    37.1 ft. - Roots Fine Joint, from 02 to 03 o'clock, within 8 inches of joint: YES

  • Deposits Settled Compacted,  10 %of cross sectional area, from 04 to 06 o'clock,  , within 8 inches of joint: YES

    132.4 ft. - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 06 o'clock, , within 8 inches of joint: YES

  • Repair Other, within 8 inches of joint: NO - CONCRETE PATCH

    137.5 ft. - Repair Other, within 8 inches of joint: NO - CONCRETE PATCH

  • General Observation - COCKROACHES IN MH

    282.4 ft. - General Observation - COCKROACHES IN MH

Observations (20)

DistanceCodeObservation
37.1RFJ
279.8DAGS
137.5RPZCONCRETE PATCH
282.4MGOCOCKROACHES IN MH
282.4AMH01 0085
126.4TFC
282.4MGOCONNECTION AT MH 3 O'CLOCK
2CM
233.9TFC
145.6TBA
0MWL
2DAGS
0MWM
42.9TFA
0AMH01 0084
132.4DSC
279.8CM
39.2TFA
89.2TFA
179TFC

Properties (7)

additional_info
630138022822001
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-02-28T02:32:12-08:00
documentation
PRO PIPE
is_lateral_inspection
false