Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 28, 2022, 10:11 AM
  • 01 0083_01 0082_02282022_032249.mp4

Date
02/28/2022
W/O
941336
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00209
PipeID
P00752
Time
2:11 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9887
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
FLORENCE-GRAHAM
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_941336_TV01255_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0083
Downstream MH
01 0082
Dir. of Survey
Downstream
Length Surveyed
247.6 ft.
Total Length
247.6 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
3
O&M Quick
4131
O&M Rating
9
Overall Index
3
Overall Quick
Overall Rating
12
Pipe schematic from manhole 01 0083 to 01 0082
MH: 01 0083MH: 01 0082downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 00832 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. MGO - General Observation - COCKROACHES IN MH18.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start47.7 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"82.2 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"112.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"126.4 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"144.2 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"168.1 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"168.1 ft. RMC - Roots Medium Connection, from 07 to 11 o'clock, 10 %, within 8 inches of joint: YES197.4 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"209 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"233 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"245.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish245.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish247.6 ft. MGO - General Observation - COCKROACHES IN MH247.6 ft. AMH - Downstream Manhole, Survey Ends - 01 0082

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    2 ft. - General Observation - COCKROACHES IN MH

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    18.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Connection, from 07 to 11 o'clock, 10 %, within 8 inches of joint: YES

    168.1 ft. - Roots Medium Connection, from 07 to 11 o'clock, 10 %, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MH

    247.6 ft. - General Observation - COCKROACHES IN MH

Observations (20)

DistanceCodeObservation
168.1TFA
2DAGS
209TFA
47.7TFA
233TFA
168.1RMC
144.2TFA
18.5CM
2MGOCOCKROACHES IN MH
245.9DAGS
197.4TFA
126.4TFA
247.6MGOCOCKROACHES IN MH
247.6AMH01 0082
0MWL
245.9CM
0MWM
0AMH01 0083
112.7TFC
82.2TFA

Properties (7)

additional_info
630138022822001
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-02-28T02:11:14-08:00
documentation
PRO PIPE
is_lateral_inspection
false