Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 28, 2022, 11:01 AM
  • 01 0080_01 0079_02282022_041748.mp4

Date
02/28/2022
W/O
941336
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00209
PipeID
P00749
Time
3:01 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9887
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
FLORENCE-GRAHAM
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_941336_TV01255_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0079
Downstream MH
01 0080
Dir. of Survey
Upstream
Length Surveyed
327 ft.
Total Length
327 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole 01 0079 to 01 0080
MH: 01 0079MH: 01 0080upstream0 ft. AMH - Upstream Manhole, Survey Ends - 01 00800 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MH2.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish2.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish56 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"98.5 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"124.9 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"151.2 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"193.2 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"233.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start259.2 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"288.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"325 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start327 ft. MGO - General Observation - COCKROACHES IN MH327 ft. AMH - Downstream Manhole, Survey Begins - 01 0079327 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK327 ft. MWL - Water Level, 20 %of cross sectional area327 ft. MWM - Water Mark, 50 %of cross sectional area

Observation photos (4)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    93.7 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    327 ft. - General Observation - COCKROACHES IN MH

Observations (19)

DistanceCodeObservation
2DAGS
0MGOCOCKROACHES IN MH
133.8TFA
67.8TFA
324.7CM
271TFC
0AMH01 0079
327AMH01 0080
38.1TFC
0MGOCONNECTION AT MH 3 O'CLOCK
0MWL
93.7CM
175.8TFA
327MGOCONNECTION AT MH 3 O'CLOCK
327MGOCOCKROACHES IN MH
202.1TFA
228.5TF
0MWM
324.7DAGS

Properties (7)

additional_info
630138022822001
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-02-28T03:01:49-08:00
documentation
PRO PIPE
is_lateral_inspection