Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 17, 2022, 08:16 AM
  • 01 0045A_01 0045_03172022_012710.mp4

Date
03/17/2022
W/O
941336
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00209
PipeID
P00709
Time
1:16 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10011
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_941336_TV01255_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
27 in.
Upstream MH
01 0045
Downstream MH
01 0045A
Dir. of Survey
Upstream
Length Surveyed
157.4 ft.
Total Length
157.4 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 01 0045 to 01 0045A
MH: 01 0045MH: 01 0045Aupstream0 ft. AMH - Upstream Manhole, Survey Ends - 01 0045A0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish38.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"41.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"87.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"90.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"143.1 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"145.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"155.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start157.4 ft. MGO - General Observation - COCKROACHES IN MH157.4 ft. MWM - Water Mark, 10 %of cross sectional area157.4 ft. AMH - Downstream Manhole, Survey Begins - 01 0045157.4 ft. MWL - Water Level, 5 %of cross sectional area157.4 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (3)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    157.4 ft. - General Observation - COCKROACHES IN MH

Observations (16)

DistanceCodeObservation
118.6TFC
0MGOCOCKROACHES IN MH
14.3TFC
155.4CM
0MWM
157.4AMH01 0045A
2CM
67.2TFC
0AMH01 0045
70.1TFC
115.6TFC
157.4MGOCOCKROACHES IN MH
157.4MGOCONNECTION AT MH 9 O'CLOCK
0MWL
0MGOCONNECTION AT MH 3 O'CLOCK
11.7TFC

Properties (7)

additional_info
630138031622201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-03-17T01:16:00-07:00
documentation
PRO PIPE
is_lateral_inspection
false