Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 17, 2022, 05:28 AM
  • 01 0044_01 0043A_03162022_224335.mp4

Date
03/16/2022
W/O
941336
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00209
PipeID
P00707
Time
10:28 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10011
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_941336_TV01255_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
27 in.
Upstream MH
01 0043A
Downstream MH
01 0044
Dir. of Survey
Upstream
Length Surveyed
325.2 ft.
Total Length
325.2 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 01 0043A to 01 0044
MH: 01 0043AMH: 01 0044upstream0 ft. AMH - Upstream Manhole, Survey Ends - 01 00440 ft. MGO - General Observation - CONNECTION AT MH 3, 9 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MH2.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish53.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"56.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"105.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"107.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"153.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"156.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"205.2 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"208.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"252.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start256.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"259 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"304.9 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"307.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"325.2 ft. MGO - General Observation - CONNECTION AT MH 3, 9 O'CLOCK325.2 ft. MWL - Water Level, 10 %of cross sectional area325.2 ft. MGO - General Observation - COCKROACHES IN MH325.2 ft. MWM - Water Mark, 10 %of cross sectional area325.2 ft. AMH - Downstream Manhole, Survey Begins - 01 0043A

Observation photos (3)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    72.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    325.2 ft. - General Observation - COCKROACHES IN MH

Observations (22)

DistanceCodeObservation
66.2TFC
20.3TFA
325.2AMH01 0044
72.5CM
18.1TFC
0MGOCONNECTION AT MH 3, 9 O'CLOCK
217.3TFC
268.9TFC
171.3TFC
0MWL
0MGOCOCKROACHES IN MH
271.5TFC
120TFC
168.3TFC
68.5TFC
325.2MGOCONNECTION AT MH 3, 9 O'CLOCK
325.2MGOCOCKROACHES IN MH
0MWM
219.9TFC
117.1TFC
322.6CM
0AMH01 0043A

Properties (7)

additional_info
630138031622201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-03-16T22:28:33-07:00
documentation
PRO PIPE
is_lateral_inspection
false