Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 17, 2022, 05:05 AM
  • 01 0042A_01 0042_03162022_221951.mp4

Date
03/16/2022
W/O
941336
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00209
PipeID
P00704
Time
10:05 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10011
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_941336_TV01255_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
12 in.
Upstream MH
01 0042
Downstream MH
01 0042A
Dir. of Survey
Upstream
Length Surveyed
344.9 ft.
Total Length
344.9 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 01 0042 to 01 0042A
MH: 01 0042MH: 01 0042Aupstream0 ft. MGO - General Observation - CONNECTION AT MH 3, 9 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. AMH - Upstream Manhole, Survey Ends - 01 0042A1.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish1.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish70.6 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"73.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"103.6 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"109.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"241.6 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"244.6 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"247.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"296.2 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"298.8 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"337.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start342.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start344.9 ft. MWM - Water Mark, 15 %of cross sectional area344.9 ft. MWL - Water Level, 10 %of cross sectional area344.9 ft. AMH - Downstream Manhole, Survey Begins - 01 0042

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    344.9 ft. - General Observation - COCKROACHES IN MH

Observations (19)

DistanceCodeObservation
0MWM
344.9MGOCONNECTION AT MH 3, 9 O'CLOCK
2DAGS
0MWL
343.6DAGS
7.3CM
97.6TFC
274.3TFC
241.3TFC
343.6CM
46.1TFA
103.3TBA
271.6TFC
48.7TFC
0AMH01 0042
235.6TFC
344.9MGOCOCKROACHES IN MH
100.3TFC
344.9AMH01 0042A

Properties (7)

additional_info
630138031622201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-03-16T22:05:39-07:00
documentation
PRO PIPE
is_lateral_inspection
false