Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 17, 2022, 09:51 AM
  • 01 0036C_01 0036B_03172022_025842.mp4

Date
03/17/2022
W/O
941336
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00209
PipeID
P00696
Time
2:51 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10011
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_941336_TV01255_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
27 in.
Upstream MH
01 0036C
Downstream MH
01 0036B
Dir. of Survey
Downstream
Length Surveyed
99.4 ft.
Total Length
99.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 01 0036C to 01 0036B
MH: 01 0036CMH: 01 0036Bdownstream0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. AMH - Upstream Manhole, Survey Begins - 01 0036C0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. MWM - Water Mark, 15 %of cross sectional area14.1 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"26 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"35.4 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"40.9 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"97.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish99.4 ft. AMH - Downstream Manhole, Survey Ends - 01 0036B99.4 ft. MGO - General Observation - COCKROACHES IN MH99.4 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (3)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    99.4 ft. - General Observation - COCKROACHES IN MH

Observations (14)

DistanceCodeObservation
0MGOCOCKROACHES IN MH
0AMH01 0036C
26TFC
99.4AMH01 0036B
2DAGS
99.4MGOCOCKROACHES IN MH
99.4MGOCONNECTION AT MH 3 O'CLOCK
40.9TF
97.6DAGS
0MWL
35.4TB
2MWM
14.1TF
0MGOCONNECTION AT MH 3 O'CLOCK

Properties (7)

additional_info
630138031622201
custom_field_three
RFIR/LIGHT GREASE
custom_field_two
3
customer
1
datetime
2022-03-17T02:51:29-07:00
documentation
PRO PIPE
is_lateral_inspection
false