Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 25, 2022, 10:14 AM
  • 01 0098_01 0097_02252022_033403.mp4

Date
02/25/2022
W/O
941336
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00209
PipeID
P00767
Time
2:14 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9886
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
FLORENCE-GRAHAM
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
03
Purpose
Routine Assessment
Project
RFIR_WO_941336_TV01255_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
01 0097
Downstream MH
01 0098
Dir. of Survey
Upstream
Length Surveyed
284.6 ft.
Total Length
284.6 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 01 0097 to 01 0098
MH: 01 0097MH: 01 0098upstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. AMH - Upstream Manhole, Survey Ends - 01 00981.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish1.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish90 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"136.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"163.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"212.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"249.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start280.1 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES282.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start284.6 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK284.6 ft. AMH - Downstream Manhole, Survey Begins - 01 0097284.6 ft. MGO - General Observation - COCKROACHES IN MH284.6 ft. MWM - Water Mark, 10 %of cross sectional area284.6 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (5)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    4.5 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    35.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    284.6 ft. - General Observation - COCKROACHES IN MH

Observations (17)

DistanceCodeObservation
148.2TFC
283.2DAGS
283.2CM
0MGOCONNECTION AT MH 9 O'CLOCK
2DAGS
284.6MGOCONNECTION AT MH 9 O'CLOCK
0AMH01 0097
72.2TFC
284.6MGOCOCKROACHES IN MH
0MGOCOCKROACHES IN MH
194.6TFC
121.5TFC
35.4CM
0MWM
4.5CM
0MWL
284.6AMH01 0098

Properties (7)

additional_info
630138022422203
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-02-25T02:14:48-08:00
documentation
PRO PIPE
is_lateral_inspection
false