Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 25, 2022, 11:32 AM
  • 01 0092_01 0091_02252022_044440.mp4

Date
02/25/2022
W/O
941336
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00209
PipeID
P00761
Time
3:32 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9886
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
FLORENCE-GRAHAM
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_941336_TV01255_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
01 0092
Downstream MH
01 0091
Dir. of Survey
Downstream
Length Surveyed
323.4 ft.
Total Length
323.4 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 01 0092 to 01 0091
MH: 01 0092MH: 01 0091downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 00920 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MH2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start82.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"128.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"219.1 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"226.9 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"321.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish321.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish323.4 ft. AMH - Downstream Manhole, Survey Ends - 01 0091323.4 ft. MGO - General Observation - COCKROACHES IN MH323.4 ft. MGO - General Observation - CONNECTION AT MH 3 AND 9 O'CLOCK

Observation photos (4)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    323.4 ft. - General Observation - COCKROACHES IN MH

Observations (16)

DistanceCodeObservation
226.9TFA
0AMH01 0092
321.2CM
0MGOCONNECTION AT MH 3 O'CLOCK
2DAGS
219.1TFC
128.9TFC
321.2DAGS
82.9TFC
323.4AMH01 0091
2CM
323.4MGOCOCKROACHES IN MH
323.4MGOCONNECTION AT MH 3 AND 9 O'CLOCK
0MWM
0MWL
0MGOCOCKROACHES IN MH

Properties (7)

additional_info
630138022422203
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-02-25T03:32:29-08:00
documentation
PRO PIPE
is_lateral_inspection
false