Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 28, 2022, 12:09 PM
  • 01 0076_01 0075_02282022_051718.mp4

Date
02/28/2022
W/O
941336
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00209
PipeID
P00745
Time
4:09 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9887
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
FLORENCE-GRAHAM
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_941336_TV01255_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0076
Downstream MH
01 0075
Dir. of Survey
Downstream
Length Surveyed
109 ft.
Total Length
109 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole 01 0076 to 01 0075
MH: 01 0076MH: 01 0075downstream0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 00752 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start3.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start90.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"106.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish106.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish109 ft. AMH - Downstream Manhole, Survey Ends - 01 0075109 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (2)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
90.7TFC
106.6DAGS
109AMH01 0075
109MGOCONNECTION AT MH 9 O'CLOCK
0MGOCOCKROACHES IN MH
3.5CM
0MWM
0MWL
106.6CM
2DAGS
0AMH01 0075

Properties (7)

additional_info
630138022822001
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-02-28T04:09:46-08:00
documentation
PRO PIPE
is_lateral_inspection
false