Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 1, 2022, 08:32 AM
  • 01 0073_01 0072_03012022_014736.mp4

Date
03/01/2022
W/O
941336
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00209
PipeID
P00742
Time
12:32 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9888
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
FLORENCE-GRAHAM
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_941336_TV01255_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0072
Downstream MH
01 0073
Dir. of Survey
Upstream
Length Surveyed
328.1 ft.
Total Length
328.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
4121
O&M Rating
8
Overall Index
2
Overall Quick
Overall Rating
11
Pipe schematic from manhole 01 0072 to 01 0073
MH: 01 0072MH: 01 0073upstream0 ft. AMH - Upstream Manhole, Survey Ends - 01 00730 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MH1.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish1.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish61.4 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"106.2 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"147.5 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"206.3 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"206.3 ft. RFC - Roots Fine Connection, from 01 to 04 o'clock250.1 ft. RFC - Roots Fine Connection, from 01 to 04 o'clock250.1 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"288.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"326.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start326.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start328.1 ft. MWM - Water Mark, 50 %of cross sectional area328.1 ft. AMH - Downstream Manhole, Survey Begins - 01 0072328.1 ft. MWL - Water Level, 40 %of cross sectional area

Observation photos (5)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Roots Fine Connection, from 01 to 04 o'clock

    78 ft. - Roots Fine Connection, from 01 to 04 o'clock

  • Roots Fine Connection, from 01 to 04 o'clock

    121.8 ft. - Roots Fine Connection, from 01 to 04 o'clock

  • General Observation - COCKROACHES IN MH

    328.1 ft. - General Observation - COCKROACHES IN MH

Observations (18)

DistanceCodeObservation
121.8TFA
328.1AMH01 0073
2CM
2DAGS
121.8RFC
0MWM
326.2CM
328.1MGOCONNECTION AT MH 3 O'CLOCK
78RFC
180.6TFA
326.2DAGS
266.7TFC
0AMH01 0072
0MWL
328.1MGOCOCKROACHES IN MH
221.9TFA
78TFA
39.8TFC

Properties (7)

additional_info
630138022822201
custom_field_three
MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2022-03-01T00:32:55-08:00
documentation
PRO PIPE
is_lateral_inspection
false