Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 1, 2022, 07:21 AM
  • 01 0072_01 0071_03012022_003248.mp4

Date
02/28/2022
W/O
941336
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00209
PipeID
P00741
Time
11:21 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9888
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
FLORENCE-GRAHAM
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_941336_TV01255_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0072
Downstream MH
01 0071
Dir. of Survey
Downstream
Length Surveyed
330.4 ft.
Total Length
330.4 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
3121
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
9
Pipe schematic from manhole 01 0072 to 01 0071
MH: 01 0072MH: 01 0071downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 00720 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start5.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start109.3 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"119.9 ft. RFJ - Roots Fine Joint, at 01 o'clock, within 8 inches of joint: YES154.4 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"208.9 ft. RML - Roots Medium Lateral, from 08 to 11 o'clock, 15 %, within 8 inches of joint: YES208.9 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"250.3 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"301.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"328.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish328.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish330.4 ft. AMH - Downstream Manhole, Survey Ends - 01 0071330.4 ft. MGO - General Observation - COCKROACHES IN MH330.4 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    5.8 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, at 01 o'clock, within 8 inches of joint: YES

    119.9 ft. - Roots Fine Joint, at 01 o'clock, within 8 inches of joint: YES

  • Roots Medium Lateral, from 08 to 11 o'clock, 15 %, within 8 inches of joint: YES

    208.9 ft. - Roots Medium Lateral, from 08 to 11 o'clock, 15 %, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MH

    330.4 ft. - General Observation - COCKROACHES IN MH

Observations (17)

DistanceCodeObservation
154.4TFA
208.9RML
328.8DAGS
0AMH01 0072
5.8CM
2DAGS
301.5TFC
0MWM
330.4AMH01 0071
0MWL
250.3TFA
119.9RFJ
330.4MGOCOCKROACHES IN MH
330.4MGOCONNECTION AT MH 9 O'CLOCK
208.9TFA
328.8CM
109.3TFA

Properties (7)

additional_info
630138022822201
custom_field_three
MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2022-02-28T23:21:27-08:00
documentation
PRO PIPE
is_lateral_inspection
false