Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 12, 2022, 11:00 AM
  • B 0627_B 0626_4122022_040158.mp4

Date
04/12/2022
W/O
0941294
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00107
PipeID
P09292
Time
4:00 AM
Certificate
U-1014-06022432
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3062
Sewer Name
B JOINT OUTFALL B - UNIT 8D
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Capital Improvement Program Assesment
Project
20220412MDM_JOINT_OUTFALL_B_UNIT_8D
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
B 0627
Downstream MH
B 0626
Dir. of Survey
Downstream
Length Surveyed
280.6 ft.
Total Length
280.6 ft.
Structural Index
2
Structural Quick
2300
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole B 0627 to B 0626
MH: B 0627MH: B 0626downstream0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Capped0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:10AM0 ft. MWL - Water Level, 5 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT2 ft. MGO - General Observation - MAG COAT 95%31 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE POSSIBLE 1 SEVERE AGG114 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE280 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE UNDER MAG COAT280 ft. MGO - General Observation - MAG COAT 95%280.6 ft. AMH - Downstream Manhole, Survey Ends - 4:30AM

Observation photos (4)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

  • General Observation - MAG COAT 95%

    2 ft. - General Observation - MAG COAT 95%

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE POSSIBLE 1 SEVERE AGG

    31 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE POSSIBLE 1 SEVERE AGG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

    114 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

Observations (11)

DistanceCodeObservation
31SSSBLISTERING PEELING CONCRETE POSSIBLE 1 SEVERE AGG
0MGOConn. @ Mh, 3 O' Clock. Capped
0MWM
0AMH4:10AM
280SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
2SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
280.6AMH4:30AM
0MWL
114SSSBLISTERING PEELING CONCRETE
280MGOMAG COAT 95%
2MGOMAG COAT 95%

Properties (6)

custom_field_three
BLISTERING PEELING CONCRETE UNDER 98% MAG COAT
custom_field_two
3
customer
LACSD
datetime
2022-04-12T04:00:42-07:00
documentation
MARTIN,OLIVER 111,IGNACIO
is_lateral_inspection
false