Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 7, 2022, 08:36 AM
  • 18 0376_18 0375_472022_014225.mp4

Date
04/07/2022
W/O
0946885
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00690
PipeID
P14211
Time
1:36 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3058
Sewer Name
18 NORTH NORWALK TRUNK
City
NORWALK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
25
Purpose
Capital Improvement Program Assesment
Project
20220407MDM_NORTH_NORWALK_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
18 0376
Downstream MH
18 0375
Dir. of Survey
Downstream
Length Surveyed
206.2 ft.
Total Length
206.2 ft.
Structural Index
3
Structural Quick
4A37
Structural Rating
131
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
131
Pipe schematic from manhole 18 0376 to 18 0375
MH: 18 0376MH: 18 0375downstream0 ft. AMH - Upstream Manhole, Survey Begins - 1:40AM0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MWL - Water Level, 10 %of cross sectional area6.4 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - SLIGHT10.6 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL14.6 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL14.6 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - HAIRLINE19.1 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H27 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL30.9 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES - SL30.9 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H35.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL38.9 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H43.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped50.2 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL54.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL58.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H58.4 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL61.9 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H62.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H66.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL71 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL75.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL78.8 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL83 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT87.2 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL87.6 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL93.2 ft. FC - Fracture Circumferential, from 08 to 01 o'clock, within 8 inches of joint: YES - SL94.8 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H99.1 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SL103.3 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL107.5 ft. FC - Fracture Circumferential, from 08 to 01 o'clock, within 8 inches of joint: YES - SL111.5 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL111.5 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL115.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL119.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL123.9 ft. FC - Fracture Circumferential, from 08 to 01 o'clock, within 8 inches of joint: YES - SL128.3 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES - SL131.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT136.1 ft. FC - Fracture Circumferential, from 08 to 03 o'clock, within 8 inches of joint: YES - H144.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped151.2 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL154.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL155.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL158.8 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL163.5 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL166.8 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL170.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL175.5 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL179.4 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL179.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, - SL JOINT TO JOINT179.4 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H183.2 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL183.2 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL191.5 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL195.6 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL195.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL195.6 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES - SL199.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL199.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL206.2 ft. AMH - Downstream Manhole, Survey Ends - 2:25AM

Observation photos (5)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

    35.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

    75.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

    155.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

    195.6 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

    199.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

Observations (62)

DistanceCodeObservation
71FMSL
166.8FCSL
30.9FLSL
128.3FLSL
43.9TFCCapped
62.7FLH
175.5FCSL
93.2FCSL
170.7FLSL
14.6FCSL
66.5FMSL
6.4FCSLIGHT
183.2FCSL
144.7TFCCapped
155.1FMSL
195.6FCSL
30.9FCH
195.6FLSL
38.9FCH
136.1FCH
0AMH1:40AM
103.3FCSL
87.6FCSL
191.5FCSL
61.9FCH
151.2FCSL
115.3FMSL
119.7FMSL
50.2FCSL
83FCSLIGHT
54.5FMSL
206.2AMH2:25AM
35.5FMSL
0MWM
87.2FCSL
58.4FLH
107.5FCSL
199.7FMSL
19.1FCH
0MGOConn. @ Mh, 3 O' Clock. Active
94.8FCH
163.5FCSL
10.6FCSL
75.1FMSL
199.7FLSL
111.5FCSL
131.6FMSLIGHT
154.8FLSL
158.8FCSL
123.9FCSL
179.4FCSL
179.4FLSL JOINT TO JOINT
0MWL
27FCSL
78.8FCSL
99.1FCSL
179.4FCH
195.6FLSL
14.6FCHAIRLINE
58.4FCSL
111.5FCSL
183.2FCSL

Properties (6)

custom_field_three
LONG SLIGHT FRACTURE JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2022-04-07T01:36:11-07:00
documentation
MARTIN,REVELES,IGNACIO
is_lateral_inspection
false