Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 14, 2022, 07:59 AM
  • 05 1605_05 1604_03142022_012311.mp4

Date
03/14/2022
W/O
941473
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00551
PipeID
P06829
Time
12:59 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9958
Sewer Name
05 203RD STREET TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
27
Purpose
Routine Assessment
Project
RFIR_WO_941473_TV05176_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
15 in.
Upstream MH
05 1605
Downstream MH
05 1604
Dir. of Survey
Downstream
Length Surveyed
294.4 ft.
Total Length
294.4 ft.
Structural Index
4
Structural Quick
4G3B
Structural Rating
215
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
215
Pipe schematic from manhole 05 1605 to 05 1604
MH: 05 1605MH: 05 1604downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 16050 ft. MWM - Water Mark, 10 %of cross sectional area4 ft. CH2 - Crack Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Start11.9 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 8"40.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8"83.5 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"93 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8"153.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8"185.9 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 8"209.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8"210.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start210.5 ft. CH2 - Crack Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish269.7 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 8"294.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish294.4 ft. AMH - Downstream Manhole, Survey Ends - 05 1604

Observation photos (5)

  • Crack Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    4 ft. - Crack Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 8"

    11.9 ft. - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 8"

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"

    83.5 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    210.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 8"

    269.7 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 8"

Observations (16)

DistanceCodeObservation
4CH2
153.2TF
210.5CM
185.9TFA
40.6TF
209.9TF
83.5TB
11.9TBA
93TF
0MWL
269.7TB
0AMH05 1605
294.4CM
210.5CH2
294.4AMH05 1604
0MWM

Properties (7)

additional_info
6300980314220001
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-03-14T00:59:38-07:00
documentation
PRO PIPE
is_lateral_inspection
false