Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 14, 2022, 08:24 AM
  • 05 1604_05 1603_03142022_014145.mp4

Date
03/14/2022
W/O
941473
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00551
PipeID
P06828
Time
1:24 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9958
Sewer Name
05 203RD STREET TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
27
Purpose
Routine Assessment
Project
RFIR_WO_941473_TV05176_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
15 in.
Upstream MH
05 1604
Downstream MH
05 1603
Dir. of Survey
Downstream
Length Surveyed
300 ft.
Total Length
300 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
177
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
177
Pipe schematic from manhole 05 1604 to 05 1603
MH: 05 1604MH: 05 1603downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 16040 ft. MWM - Water Mark, 10 %of cross sectional area2.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start23.8 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"59.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8"114.7 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 8"275.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8"300 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish300 ft. AMH - Downstream Manhole, Survey Ends - 05 1603

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"

    23.8 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 8"

    114.7 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 8"

Observations (10)

DistanceCodeObservation
2.9CM
114.7TBA
275.9TF
23.8TB
300CM
59.2TF
0MWL
0AMH05 1604
0MWM
300AMH05 1603

Properties (7)

additional_info
6300980314220001
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-03-14T01:24:32-07:00
documentation
PRO PIPE
is_lateral_inspection
false