Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 10, 2022, 06:26 AM
  • 21 1024_21 1023_03092022_234941.mp4

Date
03/09/2022
W/O
941466
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00784
PipeID
P16124
Time
10:26 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9953
Sewer Name
21 SAN ANTONIO TRUNK
City
CLAREMONT
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_941466_TV21055_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
21 1024
Downstream MH
21 1023
Dir. of Survey
Downstream
Length Surveyed
375 ft.
Total Length
375 ft.
Structural Index
3
Structural Quick
3K26
Structural Rating
192
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
192
Pipe schematic from manhole 21 1024 to 21 1023
MH: 21 1024MH: 21 1023downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 21 10247 ft. CS - Crack Spiral, from 08 to 11 o'clock, within 8 inches of joint: YES8.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"12.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"12.6 ft. CS - Crack Spiral, from 08 to 11 o'clock, within 8 inches of joint: YES16.6 ft. CS - Crack Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES20.7 ft. CS - Crack Spiral, from 08 to 11 o'clock, within 8 inches of joint: YES24.9 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES59 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"61.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"62.4 ft. CS - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES74.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start108.6 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"111.6 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"175.2 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"177.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"241.6 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"243.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"307.6 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"310.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"375 ft. AMH - Downstream Manhole, Survey Ends - 21 1023375 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish375 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK375 ft. MGO - General Observation - GIS CALLS FOR 369'

Observation photos (7)

  • Crack Spiral, from 08 to 11 o'clock, within 8 inches of joint: YES

    7 ft. - Crack Spiral, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 08 to 11 o'clock, within 8 inches of joint: YES

    12.6 ft. - Crack Spiral, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES

    16.6 ft. - Crack Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 08 to 11 o'clock, within 8 inches of joint: YES

    20.7 ft. - Crack Spiral, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    24.9 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

    62.4 ft. - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    74.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (26)

DistanceCodeObservation
375AMH21 1023
177.4TFC
20.7CS
375CM
74.5CM
0MWM
0MWL
375MGOCONNECTION AT MH 9 O'CLOCK
59TFC
12.6CS
307.6TFC
8.8TFC
0AMH21 1024
310.3TFC
12.1TFC
375MGOGIS CALLS FOR 369'
108.6TFC
243.3TFC
111.6TFC
16.6CS
7CS
241.6TFC
62.4CS
175.2TFC
24.9CL
61.4TFC

Properties (7)

additional_info
630098030922201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-03-09T22:26:05-08:00
documentation
PRO PIPE
is_lateral_inspection
false