Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 10, 2022, 07:39 AM
  • 21 1013_21 1012_03102022_010109.mp4

Date
03/09/2022
W/O
941466
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00784
PipeID
P16113
Time
11:39 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9953
Sewer Name
21 SAN ANTONIO TRUNK
City
CLAREMONT
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_941466_TV21055_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
21 1013
Downstream MH
21 1012
Dir. of Survey
Downstream
Length Surveyed
355.6 ft.
Total Length
355.6 ft.
Structural Index
3
Structural Quick
413I
Structural Rating
164
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
164
Pipe schematic from manhole 21 1013 to 21 1012
MH: 21 1013MH: 21 1012downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 21 10130 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 5 %of cross sectional area5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"28.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"54.9 ft. CM - Crack Multiple, from 06 to 10 o'clock, within 8 inches of joint: YES58.7 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES66.4 ft. FS - Fracture Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES80.6 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"85.4 ft. CS - Crack Spiral, from 08 to 04 o'clock, within 8 inches of joint: YES89.4 ft. CS - Crack Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES111.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start132.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"154.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"181.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"201.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"231.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"254.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"281.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"304.8 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6"311.3 ft. FM - Fracture Multiple, from 03 to 06 o'clock, within 8 inches of joint: YES332.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"355.6 ft. AMH - Downstream Manhole, Survey Ends - 21 1012355.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (7)

  • Crack Multiple, from 06 to 10 o'clock, within 8 inches of joint: YES

    54.9 ft. - Crack Multiple, from 06 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    58.7 ft. - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES

    66.4 ft. - Fracture Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 08 to 04 o'clock, within 8 inches of joint: YES

    85.4 ft. - Crack Spiral, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES

    89.4 ft. - Crack Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    111.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 03 to 06 o'clock, within 8 inches of joint: YES

    311.3 ft. - Fracture Multiple, from 03 to 06 o'clock, within 8 inches of joint: YES

Observations (25)

DistanceCodeObservation
111.6CM
80.6TFC
54.9CM
201.7TFC
0MWM
0AMH21 1013
28.1TFC
5TFC
85.4CS
154.9TFC
0MGOCONNECTION AT MH 3 O'CLOCK
355.6AMH21 1012
132.7TFC
0MWL
355.6CM
311.3FM
66.4FS
89.4CS
304.8TF
231.7TFC
332.5TFC
254.3TFC
181.5TFC
281.6TFC
58.7CM

Properties (7)

additional_info
630098030922201
custom_field_three
CRACKS, FRACTURES
custom_field_two
2
customer
1
datetime
2022-03-09T23:39:04-08:00
documentation
PRO PIPE
is_lateral_inspection
false